Measuring Time not Valid¶
| Event name | Measuring time not valid | |
|---|---|---|
| Meaning | The time stamp received from the device (device time) is different to the system time (server time). | |
| Case 1 | Behavior | Only a single message. The difference between the device time and the server time < 1 minute |
| Possible root cause | A delay on the measuring data transmission. Service restart on server, server reboot, network issues. | |
| Action | No reaction required, if this happens seldom and the system works further without any issues. In case the message appears too frequently: 1) Check the settings such as the service restart interval 2) Check the IT infrastructure |
|
| Case 2 | Behavior | Only a single message. The difference between the device time and the server time > 1 minute |
| Possible root cause | The device has restarted and it was using the last known time stamp, which was stored internally | |
| Action | No reaction required, if this happened after re-powering or re-pairing a device. In case message appears too frequently: 1) Check the IIS settings about the application recycle 2) Check the IT infrastructure |
|
| Case 3 | Behavior | Consecutive messages every interval |
| Possible root cause | Device control crashed due to low power supply: 1) Low battery status. 2) Too low supply voltage in case of an external power supply. 3) The device is subjected to very low temperatures. 4) A device malfunction. |
|
| Action | 1) Change the device battery. 2) Remove the device from the very low temperature environment and consider the use of an extension cable. 3) Check the external power supply. |
|
| Case 4 | Behavior | The message appears for different devices at the same time and the device time on different devices are the same. |
| Possible root cause | The server time has been updated. The device time and server time will mismatch. | |
| Action | Check the IT infrastructure. The server time shall not have big jumps |