Skip to content

Technical Specification

Specification overview

Sensor 1 or 2 analog inputs
Measurement range 0-1 V, 0-5 V, 0-10 V, 0-20 mA, 4-20 mA
Load voltage input: 25 kOhm
current input: 250 Ohm
Measurement accuracy +/- 0.03 % full-scale
Temperature accuracy +/- 0.02 % full-scale /°C
Sensor quality
Measurement interval 10 s ... 300 s
Power supply for sensors 24 V / 80 mA maximum
Power supply 24 VDC ±10 %
Current consumption < 160 mA
External device power supply advised 24 VDC ±10 %, 4 W minimal, > 5 W Limited Power Source
Interface 10Base-T / 100Base-TX Ethernet
PoE 802.3af-2003, Class 1
Log memory 44'000 of measurement for each channel
Startup time logger < 20 s (fixed IP address)
< 40 s (DHCP)
Input simulator function for validation Fix values for each channel
Operational temperature logger -40 ... 70 °C
Storage temperature -40 ... 85 °C
Housing Material PC-ABS
IP protection IP20
Device weight 125 g
Dimensions 110 x 119 x 22.5 mm