Skip to content

Technical specifications

Device type RMS digital output module
Range of application -40…70 °C / 0…100 %rh, Non-condensing
IP protection IP20
Storage and transport conditions -40…30 °C / 0…90 %rh
Maximum altitude of operation 2000 m.a.s.l.
Interfaces Ethernet
Protocols Modbus
Number of outputs 2
Relay switching power 50 VAC(Peak) 1 A / 50 VDC/1 A, polarity independent
Voltage output (VEX) 24 VDC (maximum current depends on the connected power supply)
Power supply
Supply voltage 24 VDC ±10 % / <100 mA
PoE: 802.3af-2003, Class 1
AC Adapter requirements 24 VDC ±10 % / 4 W nominal /<15 W
power-limited
Current consumption <100 mA
Polarity protection Yes
Start time / measurement interval
Startup time 10 s (typical)
Update frequency Interval (10 s to 15 min)
General specifications
Housing material PC (Polycarbonate)
Dimensions 108 x 89.7 x 62.2 mm
Weight 155 g
Fire protection class UL94-V0
Maximum output cable length <3 m min. Cat. 5
Conformity
EMC directives: 2014/30/EU
LVD- directives: 2014/35/EU
\ EN 61326-1
EN 61000-6-2
EN 55011
EN 55032
EN 61010-1 \
IEC 61326-1
IEC 61000-6-2
IEC CISPR 11
IEC CISPR 32
IEC 61010-1 \
\ --- \ --- \
Performance criterion: www.rotronic.com
EN 61326-1
EN 61000-6-2
EN 55011
EN 55032
EN 61010-1
IEC 61326-1
IEC 61000-6-2
IEC CISPR 11
IEC CISPR 32
IEC 61010-1
Soldering material Lead free (RoHS Directive 2014/65/EU)
FDA/GAMP directives FDA CFR 21 Part 11 / GAMP5