Send Measurement Data¶
URL: POST /rmsService/wService3.DeviceService.svc/UpdateDataJson
{
"DeviceId":
"Name":"
"Serial":
"Token":
"Values":[{
"Index":1,
"Typ":1,
"Unit":"%rh",
"Value":35.6
},
{"Index":2,
"Typ":2,
"Unit":"°C",
"Value":23.5
}]
}
| Device ID | The device ID will be provided by the RMS server after pairing the device |
|---|---|
| Name | Description of the device |
| Serial number | Serial number of the device (must be a number) |
| Token | Security token, will be provided by the RMS server after pairing the device |
| Values | Array containing the measurement values (max 8 measure values are supported) |
| Index | Measure point index 0..7 |
| Type | Measure point Type 0 = unknown/analog input 1 = Humidity 2 = Temperature 32 = CO2 48 = Pressure 49 = Differential pressure 62 = Logic input (0/1) 63 = Logic output (0/1) |
| Unit | Display unit (only applicable for type 0) |
| Value | Measure value (will be saved in float format) |
| Important: Do not send data more often than our RMS account minimal interval. Data sent to fast after the last transmission will be ignored. |
|---|