Skip to content

Send Measurement Data

URL: POST /rmsService/wService3.DeviceService.svc/UpdateDataJson

{

"DeviceId":,

"Name":"",

"Serial":,

"Token":,

"Values":[{

"Index":1,

"Typ":1,

"Unit":"%rh",

"Value":35.6

},

{"Index":2,

"Typ":2,

"Unit":"°C",

"Value":23.5

}]

}

Device ID The device ID will be provided by the RMS server after pairing the device
Name Description of the device
Serial number Serial number of the device (must be a number)
Token Security token, will be provided by the RMS server after pairing the device
Values Array containing the measurement values (max 8 measure values are supported)
Index Measure point index 0..7
Type Measure point Type
0 = unknown/analog input
1 = Humidity
2 = Temperature
32 = CO2
48 = Pressure
49 = Differential pressure
62 = Logic input (0/1)
63 = Logic output (0/1)
Unit Display unit (only applicable for type 0)
Value Measure value (will be saved in float format)
Important:
Do not send data more often than our RMS account minimal interval. Data sent to fast after the last transmission will be ignored.