Alarm Limits

Alarm limits are schemes that can be used to trigger alarms. They are useful when the same threshold values are to be used for several measuring points or further conditions for triggering of the alarm are to be added.

All alarm limits are shown that are visible to the current user on the basis of the group allocation. Unused alarm limits (no measuring point allocated) are shown with a block dot.

The following functions are available for creating and editing alarm limits:

Filter Filter the list of alarm limits on the basis of the entry
New Add new alarm limit
Delete Delete alarm limit
Save Save changes

Every alarm limit has the following properties:

ID Unique ID number (AS-xxxx)
Name Freely selectable name
Parameter The unit of the measured value must be specified correctly so that unit conversions by the system are carried out correctly
Applicable in Group in which the alarm limit can be applied
Used by Measuring points that use this alarm limit
Condition
Switch input Switch contact or virtual switch to serve as precondition whether the alarm limit is enabled or not.
E-SM-RMS-WEB-V1.3.1_Alarm Limits
Active time Time in which the alarm thresholds 1 are enabled. Outside this time the alarm thresholds 2 are enabled.
E-SM-RMS-WEB-V1.3.1_set notifications 2
Alarm thresholds 1 / 2
Enabled / Disabled Only enabled alarms are processed in the system
Lower limit Lower limit value
Upper limit Upper limit value
Hysteresis Hysteresis
Delay Delay for alarm release
Action Action that is to be carried out when the alarm is triggered (see section 5.2)