Modbus

MODBUS communication protocol

Important:
Please read out the MODBUS byte order of the RMS device with RMS-CONFIG prior to any programming.

For direct connection to other systems, the device provides a MODBUS TCP server. Following data is available via MODBUS communication:

Protocol MODBUS TCP
TCP Port 502

When reading out data from the input register select the index=-1.

MODBUS register

Device data (FC4: Read Input Registers)

10000 16 Digital inputs Unsigned 16 Bit Bit 0 = Input 1 / Bit 1 = Input 2

Measurement values (FC2: Read Discrete Inputs)

30000 2 Serial number Unsigned 32 Bit SN in Hex: e.g. 01ACCBE1 = 28101601

The RMS LAN devices (except the RMS-Converter) are based on a Little Endian memory organisation (The device firmware provides the MODBUS information starting with the most significant byte.)

31001 0 0x0000 31001 13378 0x3442
31002 13378 0x3442 31002 0 0x0000
31003 0 0x0000 31003 31300 0x7A44
31004 31300 0x7A44 31004 0 0x0000
Byte Swap (Mixed Endian) Byte and Word Swap (Big Endian)
31001 0 0x0000 31001 16948 0x4234
31002 16948 0x4234 31002 0 0x0000
31003 0 0x0000 31003 17530 0x447A
31004 17530 0x447A 31004 0 0x0000

Connection timeout: When TCP connection is open and for more than 30 seconds no communication is performed, the device automatically closes the TCP connection. In case of a communication interruption, this prevents the socket being blocked.

Additional MODBUS details can be found here: MODBUS in RMS.