Skip to content

Technical specifications

Device type RMS digital input module
Range of application -40…70 °C / 0…100 %rh, Non-condensing
IP protection IP20
Storage and transport conditions -40…30 °C / 0…90 %rh
Maximum altitude of operation 2000 m.a.s.l.
Interfaces Ethernet
Data memory 75‘000 measured values
Number of inputs 2 independent digital inputs
Input frequency Max: 0.833 Hz, btw. 1.2 s
Pulse detection time Min: 100 ms
Input circuit Logic levels: 0 V / 5-24 V
Triggering-threshold: ~3.77 V
Current consumption: <1 mA
Reed circuit Maximum load at input: 100 kΩ
Power supply
Supply voltage 24 VDC ±10 % / <100 mA1
PoE: 802.3af-2003, Class 1
Battery
Battery life The batteries of RMS devices typically last 3 years under the optimal conditions:
- Temperature = 20°C±5°C.
- Wireless signal strength >-60 dBm.
- Limited “read out data” events in the audit trail.
Current consumption <100 mA
Polarity protection Yes
Start time / measurement interval
Startup time 10 s (typical)
Logging frequency Event triggered & interval (10 s to 15 min)
General specifications
Housing material PC (Polycarbonate)
Dimensions 108 x 89.7 x 62.2 mm
Weight 200 g
Fire protection class UL94-V0
Maximum input cable length <3 m min. Cat. 5
Conformity
EMC directives: 2014/30/EU
LVD- directives: 2014/35/EU
\ EN 61326-1
EN 61000-6-2
EN 55011
EN 55032
EN 61010-1 \
IEC 61326-1
IEC 61000-6-2
IEC CISPR 11
IEC CISPR 32
IEC 61010-1 \
\ --- \ --- \
Performance criterion: www.rotronic.com
EN 61326-1
EN 61000-6-2
EN 55011
EN 55032
EN 61010-1
IEC 61326-1
IEC 61000-6-2
IEC CISPR 11
IEC CISPR 32
IEC 61010-1
Soldering material Lead free (RoHS Directive 2014/65/EU)
FDA/GAMP directives FDA CFR 21 Part 11 / GAMP5

1 Power supply requirements: 24 VDC ±10 % / >4 W / limited power source