Modbus

MODBUS communication protocol

Important:
Please read out the MODBUS byte order of the RMS device with RMS-CONFIG prior to any programming.

For direct connection to other systems, the device provides a MODBUS TCP server. To following data is available via MODBUS communication:

Protocol MODBUS TCP
TCP Port 502

When reading out data from the input register select the index=-1.

Function 04- Read Input Register

30001 Serial number Unsigned 32 Bit
30002
30003 Serial number of the probe Unsigned 32 Bit
30004
31001 Value 1 Measurement value 1 of the sensor Float 32 Bit
31002
31003 Value 2 Measurement value 2 of the sensor Float 32 Bit
31004

The measurement values are only available in floating format.

Swap mode

The swap mode defines how a float32 value is represented in MODBUS data structure. The settings must be done with the RMS-CONFIG software.

Factory settings: WORD-Swap

Example:

Value 1 (Address 31001 / 31002) 45.0 = 0x42340000
Value 2 (Address 31001 / 31002) 1000.0 = 0x447A0000

The following website helps for conversion: https://www.h-schmidt.net/FloatConverter/IEEE754de.html

The RMS LAN devices (except the RMS-Converter) are based on a Little Endian memory organisation (The device firmware provides the MODBUS information starting with the most significant byte.)

31001 0 0x0000 31001 13378 0x3442
31002 13378 0x3442 31002 0 0x0000
31003 0 0x0000 31003 31300 0x7A44
31004 31300 0x7A44 31004 0 0x0000
Byte Swap (Mixed Endian) Byte and Word Swap (Big Endian)
31001 0 0x0000 31001 16948 0x4234
31002 16948 0x4234 31002 0 0x0000
31003 0 0x0000 31003 17530 0x447A
31004 17530 0x447A 31004 0 0x0000

Software Compatibility

The logger is designed for use with the RMS server software (local installation or Rotronic Cloud). The data logger can alternatively also be operated with the RMS-Configuration software (standalone software).

Connection timeout: When TCP connection is open and for more than 30 seconds no communication is performed, the device automatically closes the TCP connection. In case of a communication interruption, this prevents the socket being blocked.

Additional MODBUS details can be found here: MODBUS in RMS.