Technical specification¶
| Device type | Humidity and temperature probe |
|---|---|
| Range of application | Electronic: -40…+85 °C / 0…100 %rh Sensor head: -100…+200 °C1 / 0…100 %rh Continuous Load: 190 °C max |
| Mechanical configuration | See variants |
| IP protection | IP65 |
| Power supply / connection | |
| Power supply (VDD) | 3.3…15 VDC ±1 % |
| Current consumption | <3 mA |
| Maximum inrush current | <200 mA for 50 µs |
| Maximum operating current | <3 mA |
| Polarity protection | Mechanical protection |
| Humidity measurement | |
| Sensor | ROTRONIC HYGROMER® HT-1 |
| Measurement range | 0…100 %rh |
| Measurement accuracy | ±0.8 %rh at 10…30 °C |
| Long term stability | <1 %rh / year |
| Sensor response time | Typically 30 sec, for 63 % of 35 to 80 %rh step (1 m/s wind speed at sensor) |
| Temperature measurement | |
| Sensor | Pt100 RTD, IEC 751 1/3 Class B |
| Measurement range | -100…+200 °C 1 |
| Measurement accuracy | ±0.1 °C at 10…30 °C |
| Long term stability | <0.1 °C / year |
| Sensor response time | Typically 3 min, for 63 % of the temperature change (1 m/s wind speed at sensor) |
| Calculated parameters | |
| Psychrometric calculations | None |
| Start time / measurement interval | |
| Start time | 90 ms (typical) |
| Measurement interval | 500 ms (typical) |
| Digital interface | |
| Type | UART |
| Factory default | Baud rate 19200, tolerance 2 % Parity: none Data bits: 8 Stop bits: 1 Flow control: none |
| Logic levels | Logic 0: ≤0.4 V Logic 1: ≥2…2.5 V |
| Maximum cable length | 3 m |
| Conformity | |
| CE / EMC | EMC Directive: 2014/30/EU EN 61326-1 (industrial locations) Performance criterion: www.rotronic.com |
| Soldering | Lead free (RoHS Directive 2011/65/EU) |
| FDA/GAMP directives | Compatible |
| Accepted environmental conditions | |
| Storage/transportation | -50…+100 °C / 0…100 %rh, non-condensing |
| Range of application (electronics) | -50…+100 °C 0…100 %rh, non-condensing |
| Maximum wind velocity | See filter specifications |
| Critical gases | Please consider the sensor data sheet of the HT-1 sensor. Please contact Rotronic support for that. |
1The peak load at 200 °C is 100 h maximum. Continuous Load 190 °C maximum. See the sensor data sheet for detailed information on the pollution loads.