Technical specification

Device type Humidity and temperature probe
Range of application Electronic: -40…+85 °C / 0…100 %rh
Sensor head: -100…+200 °C1 / 0…100 %rh
Continuous Load: 190 °C max
Mechanical configuration See variants
IP protection IP65
Power supply / connection
Power supply (VDD) 3.3…15 VDC ±1 %
Current consumption <3 mA
Maximum inrush current <200 mA for 50 µs
Maximum operating current <3 mA
Polarity protection Mechanical protection
Humidity measurement
Sensor ROTRONIC HYGROMER® HT-1
Measurement range 0…100 %rh
Measurement accuracy ±0.8 %rh at 10…30 °C
Long term stability <1 %rh / year
Sensor response time Typically 30 sec, for 63 % of 35 to 80 %rh step (1 m/s wind speed at sensor)
Temperature measurement
Sensor Pt100 RTD, IEC 751 1/3 Class B
Measurement range -100…+200 °C 1
Measurement accuracy ±0.1 °C at 10…30 °C
Long term stability <0.1 °C / year
Sensor response time Typically 3 min, for 63 % of the temperature change (1 m/s wind speed at sensor)
Calculated parameters
Psychrometric calculations None
Start time / measurement interval
Start time 90 ms (typical)
Measurement interval 500 ms (typical)
Digital interface
Type UART
Factory default Baud rate 19200, tolerance 2 %
Parity: none
Data bits: 8
Stop bits: 1
Flow control: none
Logic levels Logic 0: ≤0.4 V
Logic 1: ≥2…2.5 V
Maximum cable length 3 m
Conformity
CE / EMC EMC Directive: 2014/30/EU
EN 61326-1 (industrial locations)
Performance criterion: www.rotronic.com
Soldering Lead free (RoHS Directive 2011/65/EU)
FDA/GAMP directives Compatible
Accepted environmental conditions
Storage/transportation -50…+100 °C / 0…100 %rh, non-condensing
Range of application (electronics) -50…+100 °C
0…100 %rh, non-condensing
Maximum wind velocity See filter specifications
Critical gases Please consider the sensor data sheet of the HT-1 sensor. Please contact Rotronic support for that.

1The peak load at 200 °C is 100 h maximum. Continuous Load 190 °C maximum. See the sensor data sheet for detailed information on the pollution loads.