Skip to content

Send Measurement Data

URL: POST /rmsService/wService3.DeviceService.svc/UpdateDataJson

{

"DeviceId":,

"Name":"",

"Serial":,

"Token":,

"Values":[{

"Index":1,

"Typ":1,

"Unit":"%rh",

"Value":35.6

},

{"Index":2,

"Typ":2,

"Unit":"°C",

"Value":23.5

}]

}

Important! For the first pairing process and must be set to 0!

Device ID The device ID will be provided by the RMS server after pairing the device
Name Description of the device
Serial number Serial number of the device (must be a number)
Token Security token, will be provided by the RMS server after pairing the device
Values Array containing the measurement values (max 8 measure values are supported)
Index Measure point index 0..7
Type Measure point Type
0 = unknown/analog input
1 = Humidity
2 = Temperature
32 = CO2
48 = Pressure
49 = Differential pressure
62 = Logic input (0/1)
63 = Logic output (0/1)
Unit Display unit (only applicable for type 0)
Value Measure value (will be saved in float format)
Important:
Do not send data more often than our RMS account minimal interval. Data sent to fast after the last transmission will be ignored.

When using the Rotronic Cloud, the URL would be: http://rms.rotronic.com/wService/wService3.DeviceService.svc/UpdateDataJson.