Change Log/Release Notes

Version Overview

Please find below the meaning of the version.

  • 1: Major version number.
  • X.1: Minor version number.
  • X.X.1: Bug fix or specific update version number.

Rotronic Tracking System

Rotronic use a tracking system to monitor bugs, features, improvements and change requests. This tracking system is the basis for any software, hardware and firmware User Requirement Specification based upon the GAMP©5 validation model. Each point will be recognized with an ID (eg. RMS-XXX). A description and details are attributed to each point within the tracking system. All changes documented within the RMS Release Notes will have an ID number and a description.

Important
The Change Log/Release Notes are valid for
- RMS-CONVERTER-100 (HW version)
- RMS-CONVERTSW-100 (SW version)

Version V2.2.0

Release Details

The RMS-CONVERTSW-100 is introduced and it

  • is a software product that has the same aim as the RMS-CONVERTER-100, to integrate non-RMS devices into the RMS.
  • acts as an translater between these devices and the RMS - by transmission of different device protocols to the RMS and back.
  • can be installed on a high performance server within the customer network that decreases the risk of default / probability of failure.

Main topics of this version

  • Converter solution as a software
  • Integration of OPC UA interface (Converter as a UA client)

New features/improvements

RMS-9369A Run Converter software as windows service
RMS-9370A Read from OPC UA
RMS-9530A Run as windows service - Disable UDP discovery
RMS-10621A Run as windows service - include default settings.json in zip file
RMS-10644A Enable Modubs GUI on demand

Bugfixes

RMS-10819A AutoPairing always active
RMS-10876A All OPC monitoring runs on the same thread
RMS-10880A Second OPC server not working at Daichii

Version V2.0.0

Important:
The Version 2.0.0 is not backward compatible to any previous version. This version cannot be applied onto RMS-Converter running within a productive RMS system.
If an update is required, please contact our customer support. We can update the RMS-Converter inhouse at Rotronic.
The version 2.0.0 contain all functionality of the previous version 1.9.0 plus the following added features.

Release Details

New features/improvements

RMS-CONVERTER-5705A HTTPS Gateway
RMS-CONVERTER-8186A Converter communicates via HTTPS to RMS

Version V1.9.0

Release Details

The main target of this firmware version has been to:

  • Integrate the ALMO alarm monitor device with modbus TCP functionality. With this setup, it is possible to integrate radiation measurement into the RMS.
  • Possibility to configure a proxy server on the RMS-CONVERTER-100.

Bug Fixes

RMS-CONVERTER-5902A Integration of Almo Panel.
RMS-CONVERTER-5707A Configure proxy server on the converter.

Version V1.8.0

Release Details

The main target of this firmware version has been to integrate the GUI Improvements and optimize the Modbus editor formula for scaling.

Improvement

RMS-CONVERTER-3292A GUI improvements

Bug Fixes

RMS-CONVERTER-3285A Wrong modbus editor formula for scaling

Version V1.7.0

Release Details

The main target of this firmware version has been to adapt the RMS-CONVERTER-100 to work within an Azure environment including a traffic manager.

New Features

RMS-CONVERTER-569A Under settings, a button to restart the converter has been added.
RMS-CONVERTER-571A Comment field added for each line within the modbus map.

Improvement

RMS-CONVERTER-575A DNS secondary

Bug Fixes

RMS-CONVERTER-567A When using a special character in a modbus map, the RMS-CONVERTER blocks.
RMS-CONVERTER-570A Increase the maximum number of readable information per device driver
RMS-CONVERTER-1295A Secondary DNS server is used - wrong content get's saved to /etc/resolv.conf

Version V1.6.0

Release Details

The main target of this firmware version has been to integrate the AirNet II Particle Counter into the Firmware.

New Features

RMS-CONVERTER-2924 In case of a first operation and integration into RMS via Converter, or in case of short power interrupt, the particle counter Airnet II need to be reinitiated by a modbus order, that enables/re-enables the particle counter. For that reason, a new command ‘Write single coil’ with starting address and switching status IS implemented into the Modbus editor of the Converter. Every interval this order is sent out from the converter to the particle counter. The modbus order cannot be linked to any RMS function. It works independent between particle counter and converter.

Version V1.5.0

Release Details

The main target of this firmware version has been to correct existing bugs that can occur when an RMS-CONVERTER-100 and a HygroLog NT/HL-NT are integrated into a system.

New Features

RMS-CONVERTER-2646 In protected IT infrastructures, the use of a CA certificate could be mandatory to identify that the RMS-CONVERTER-100 is a permitted network participant. For that reason such a CA certificate can be uploaded to the RMS-Converter.

Improvements

RMS-CONVERTER-2850 Modbus Editor – The Signed Integer as a further number format is added.

Bug Fixes

RMS-CONVERTER-2530 & 2545 HL-NT input 7 not transmitting probe serial number.
RMS-CONVERTER-2429 Validation issue with Battery test for HL-NT. The HL-NT units have PoE functionality. The battery levels shown on the HL-NT's are incorrect. The information about the battery level is not displayed anymore.
RMS-CONVERTER-2409, 2426, 2222 Within the audit trail, the event "Probe replaced" appears without any probes being replaced.
Important due to the range of HygroLog and HL devices as well as the range of docking stations, Rotronic cannot fully guaranty that this bug is corrected for the entire range of products.
RMS-CONVERTER-2425 Data gaps by HL-NT devices (only data gaps on RMS, data is available on memory card).
RMS-CONVERTER-2575 When the probe on a HL-NT is disconnected, it shows probe replaced (SNxxx -> 0) in the audit trail, whereas a sensor error should appear.
RMS-CONVERTER-2496 Data gaps when reading out digital inputs.
Note: Update to RMS Software V2.2 is necessary.

Version V1.4.0

Release Details

This firmware version has been programmed to implement the Modbus TCP Editor to allow for easy integration of 3rd party devices in the RMS environment.

New Features

RMS-2341 Modbus Editor to integrate Modbus TPC devices (only Ethernet devices) into the RMS.

Bug Fixes

RMS-2587 RMS-Converter causes a data gap after an RMS software restart, which is caused by an empty device list on first query (only visible as of the RMS V2.0.0).

Version V1.3.0

New Features

RMS-793 Encrypted communication between Webservice and Converter.

Improvements

RMS-1112 Adjustment for differential pressure devices implemented: PF4 first generation.
RMS-795 Adjustment for differential pressure devices implemented: PF4/5 second generation, CRP5.
RMS-831 Implemented two new devices: RMS-8ADC-L-R, RMS-4RTD-L-R.
RMS-1012 Implemented a new device: RedLion E3-16ISOTC.
RMS-832 Login window integration. During the first 10min from the startup, the default password and user can be used.

Bug Fixes

RMS-787 Automatic restart function after system break down. Improved startup function for the OS.
RMS-740 HL NT audit trail message “Probe replaced SNxxxx to SN0 corrected”.
RMS-829 By configuration the RMS-8ADC-L-R unit is mv, it shall be mA.
Channel number from the RMS-8ADC-L-R is 0 to 7. In RMS Webservice was it 1 to 8. Corrected to 0 to 7 in RMS Webservice.
RMS-849 DNS address get reset to “8.8.8.8” after reboot.
RMS-1104 Converter deleted HL-NT log files that are older than 1 week.
RMS-939 PF5/4 reconnection after network issues.

Updated: 26.01.2026