Measuring Point Settings

The RMS device has the following properties and setting possibilities:

Info
ID Unique ID for the measuring point (MPT-xx)
Type Measuring point type or parameter
Measuring element (e.g. HygroClipD) that is connected directly to the device.
- Psychrometric Calculation
Psychrometric calculation from humidity and temperature.
- Arithmetic Calculation
Arithmetic calculation (e.g. difference, sum, average, PT1 filter, etc.)
- Virtual button
Logical switch that can be operated by the user directly.
- System measuring point
A system measuring point counts events and can be monitored with an alarm threshold like a normal measuring point. It can also be used to measure the signal strength.
Types of system measuring points:
- Switch input counter
Number of state changes of a logical input1
- Alarm time counter
Duration of the alarm state2 of a measuring point.
- Measuring point alarm counter
Number of measured values of a measuring point in alarm state3
- Device refresh counter
Counts when a device sends new measured values
- Signal strength
Measures the signal strength and writes it in the database like a measured value
- Pending reminders
- Pending warnings
- Pending alarms
- Pending errors
- CPU load
CPU load in %
- Memory load
Memory load in %
- Measuring point updates
Number of updated measuring points (valid for all measuring points, also calculations and counters)
- Pending commands
Number of Pending commands
- Software exceptions
Number of software errors
- Active users
Number of active users based on RMS pages loaded
- Page loads
Number of loaded RMS pages
Status Measuring point is enabled in the system.
- Disabled
The system does not receive any data from the measuring point and alarms are also not triggered.
Serial number Serial number of the probe (only in the case of interchangeable RMS probes)
Device Name and ID of the device, including direct link to device settings
Last refresh Time that has passed since the system last received data from the measuring point
Settings
Name Freely selectable measuring point name
Regulation status Freely selectable regulation status (GMP / GLP / etc.)
Comment Freely selectable comment
Details Settings for a calculated measuring point or system counter
Group(s) Group allocation (more than one group can be specified)
Alarm
Mode No alarm evaluation.
- Measuring point
The alarm limits are defined directly for the measuring point.
- Alarm triggers
The alarm limits are defined as alarm scheme (alarm triggers).
Warning
Enabled / Disabled Only enabled alarms are processed in the system
Lower limit Lower limit value
Upper limit Upper limit value
Hysteresis Hysteresis
Delay Delay in alarm notification
Alarm
Enabled / Disabled Only enabled alarms are processed in the system
Lower limit Lower limit value
Upper limit Upper limit value
Hysteresis Hysteresis
Delay Delay in alarm notification

1 Logical inputs can only have the states "1" or "0".

2 Alarm states are: "Warning" or "Alarm"

3 Alarm states are: "Warning" or "Alarm"

The following functions are available for editing measuring points:

New Add new measuring point
Archive All information of the measuring point data set is archived and can be viewed in the archive. The data archive is described in the E-OM-RMS-WEB document.
Delete Delete measuring point irretrievably.4 5
To delete a device, it is also necessary to enter a text in order to prevent accidental deletion of a device.
Save Save measuring point settings

4 So that measuring points can be deleted, this function must be enabled in the system settings.

5 Alarms relating to this measuring point are ended automatically and labels deleted from the "Layout" view.